By doing OSIM inspection of many culverts, I noticed that the most deterioration of the culverts are due to corrosion of the rebar and delamination on the soffit and walls and that is caused by ground water seepage through concrete.
Read more
The concrete pipe industry would like to make the following comments regarding the draft of standard drawings: MTOD 926.1031 and MTOD 926.1032
Comments applicable to both drawings:
Read more
1 - OPSD 3920.100 and typical PC box culvert shop drawing does not have C.J. at top and relevant note 1 may need to clarify.
2 MTO structural manual 14.1.4 noted WP be applied and extending 1000 mm beyond extent of the fill, would relevant detail be added in the MTOD?
Read more
Consulter les commentaires qu'a reçus cet avis par l'entremise du registre. Vous pouvez soit tous les télécharger, soit utiliser la fonction de recherche et de tri ci-dessous.
Certains commentaires ne seront pas affichés en ligne. Apprenez-en davantage sur l'état du commentaire et sur nos politiques relatives aux commentaires et à la protection de la vie privée.
Télécharger les commentaires
By doing OSIM inspection of…
Commenter
Documents MTOD contenant les éléments d’étanchéité des ponceaux en béton préfabriqué
commentaire ID
248
Commentant au nom de
État du commentaire
Related actions
The concrete pipe industry…
Commenter
Documents MTOD contenant les éléments d’étanchéité des ponceaux en béton préfabriqué
commentaire ID
250
Commentant au nom de
État du commentaire
Related actions
1 - OPSD 3920.100 and…
Commenter
Documents MTOD contenant les éléments d’étanchéité des ponceaux en béton préfabriqué