Commentaire
1 - OPSD 3920.100 and typical PC box culvert shop drawing does not have C.J. at top and relevant note 1 may need to clarify.
2 MTO structural manual 14.1.4 noted WP be applied and extending 1000 mm beyond extent of the fill, would relevant detail be added in the MTOD?
3 SSP599S30 does not differentiate width 600 and 900, may be it is better to convert that to a filled SP with warrant instruction in CPS.
See attachement.
Submitted 17 December 2022 9:45 PM