Comment
910.01.02.01
“The ducts, including joints, shall be watertight, vapour-tight and nonreactive with concrete, tendons, or grout. The ducts and components shall meet the requirements of Post-Tensioning System Tendon Protection Level 2 (PL-2) according to PTI/ASBI M50.3”
- All Tendon components (anchorages, caps, etc…) should meet the requirements of PL2 Protection level, not only the duct components
“Ducts for external post-tensioning shall be made from smooth, and rigid polyethylene” external PT is out of the scope of the standard, as per 910.01
Submitted March 15, 2023 1:24 PM